SGI 225KW
|
SGI 250KW
|
SGI 266KW
|
SGI 300KW
|
SGI 500KW
|
|
OUTPUT
|
|
Continuous AC Power
|
225kW
|
250kW
|
266kW
|
300kW
|
500kW
|
|
CEC Eligible AC Power 480VAC
|
225kW
|
250kW
|
266kW
|
300kW
|
500kW
|
|
Power Factor
|
>0.99
|
|
Voltage Range (-12%/+ 10%)
|
480 VAC, 3-Ph (600 VAC option)
|
Rated Current
480 VAC
600 VAC
|
271A
217A
|
301A
241A
|
320A
256A
|
360A
288A
|
600A
480A
|
|
Current Distortion
|
< 3% THD, Nom power
|
|
Frequency
|
60Hz
|
|
CEC Efficiency
|
97%
|
|
Overall Peak Efficiency1
|
97.4%
|
|
INPUT
|
|
Array Configuration
|
Monopole, Negative grounded (pos ground opt)
|
|
Max VOC2
|
625 VDC
|
|
Maximum DC Current
|
780 A
|
864 A
|
918 A
|
1036 A
|
1727 A
|
|
CEC Eligible DC Current
|
780 A
|
864 A
|
918 A
|
1036 A
|
1727 A
|
|
MPT Voltage Range3
|
300-500 VDC (285 VDC option)
|
|
CEC Full Power Voltage Range
|
300-480 VDC
|
|
PROTECTION3
|
|
AC Grid-Connection
|
Over/Under Voltage, Over Current
Over/Under Frequency, DC Ground Fault (GFDI)
|
|
AC Disconnect (Integral)
|
NEMA 3R, integral
|
DC Sub-Combiner w/Fuses
(Optional)
|
70-400A fuses available, 6-32 pole, NEMA 3R, TVSS
|
|
DC Disconnect (Integral)
|
Break load rated, NEMA 3R
|
|
ENVIRONMENTAL
|
|
Ambient Temperature
|
-40 to 50 deg C (full power)
|
|
Storage Temperature
|
-40 to 70 deg C
|
|
Cooling
|
Automatic Forced Convection
|
|
Enclosure
|
Rain Proof (UL1741)
|
|
Enclosure-Electronics
|
Sealed, IP-62
|
|
GENERAL |
|
Weight lb(kg)
|
5170lb(2350kg)
|
5170lb(2350kg)
|
5170lb(2350kg)
|
5650lb(2568kg)
|
6980lb(3173kg)
|
|
Dimensions (HxWxD)
|
79(2007) x 109(2769) x 41(1041)
|
|
Warranty
|
5 years (10, 15 and 20 yrs extended warranty available)
Preventative Maintenance and Uptime Guarantee
|
|
Communications, Optional Data Acquisition
|
RS485 Modbus RTU, Ethernet, SolrenView web-based monitoring
|
1 Fully integrated package: includes transformer, filters, fan, AC&DC disconnects, and combiner-fuse box
3 Complies with grid connection and safety standards ("Safety Features")
|