SGI 225 |
SGI 250 |
SGI 266 |
SGI 300 |
SGI 500 |
| DC INPUT |
| Absolute Maximum Input Voltage |
625 VDC |
| MPPT Input Voltage Range |
300-500 VDC |
MPPT Input Voltage Range (Low Voltage Option) |
285-500 VDC |
| Maximum Operating Input Current |
768 A |
853 A |
908 A |
1026 A |
1721 A |
Maximum Operating Input Current (Low Voltage Option) |
808 A |
898 A |
956 A |
1080 A |
1812 A |
| AC OUTPUT |
| Nominal Output Voltage |
480 or 600 VAC, 3-Ph |
| AC Voltage Range (Standard) |
-12%/+10% |
| Continuous Output Power (480/600 VAC) |
225 kW |
250 kW |
266 kW |
300 kW |
500 kW |
Continuous Output Current (480 VAC) (600 VAC) |
271 A 217 A |
301 A 240 A |
320 A 256 A |
360 A 289 A |
602 A 480 A |
| Maximum Backfeed Current |
0 A |
| Nominal Output Frequency |
60 Hz |
| Output Frequency Range |
59.3-60.5 Hz |
| Power Factor |
Unity, >0.99 |
| Total Harmonic Distortion (THD) |
<3% |
| Efficiency |
| Peak Efficiency |
98.0% |
98.0% |
98.0% |
97.9% |
97.9% |
| CEC Efficiency |
97.5% |
97.5% |
97.5% |
97.5% |
97.0% |
| Tare Loss |
28W |
28W |
28W |
28W |
32W |
| Subcombiner Options |
|
6 positions, 225-400 A 12 positions, 110-200 A 24 positions, 70-100 A |
8 positions, 225-400 A 16 positions,110-200 A 32 positions, 70-100 A |
| Temperature |
| Ambient Temp. (full power) |
-40°F to +122°F (-40°C to +50°C) |
| Storage Temperature Range |
-40°F to +158°F (-40°C to +70°C) |
| Relative Humidity (non-condensing) |
5-95% |
| Monitoring Options |
| Web-based Monitoring (Inverter Direct) |
SolrenView |
| Revenue Grade Monitoring (Integrated) |
400 A |
400 A |
400 A |
400 A |
800 A |
| Sub-Array Monitoring (SolZone) |
6 zones |
6 zones |
6 zones |
6 zones |
8 zones |
| Cellular Communication |
SolrenView AIR |
| Third Party Compatibility |
Standard via MODBUS |
Testing & Certifications
|
| Safety Listings & Certifications |
UL 1741/IEEE 1547, IEEE 1547.1, IEEE 62.41.2, IEEE 62.45, IEEE C37.90.2, CSA C22.2#107.1, FCC part 15 B |
| Maintenance outage power factor per IEEE 762-2006 |
0.1 |
| Testing Agency |
ETL |
| Warranty
|
| Standard |
5 year |
| Optional |
10, 15, 20 year; extended service agreement; uptime guarantee |
| Enclosure
|
| Transformer |
Standard, fully-integrated (internal); External optional |
| AC/DC Disconnects |
Standard, fully-integrated (internal) |
| Dimensions (H x W x D) |
79 in. x 109 in. x 41 in. (2007 mm x 2769 mm x 1041 mm) |
| Weight |
5170 lbs (2350 kg) |
5650 lbs (2568 kg) |
5650 lbs (2568 kg) |
5650 lbs (2568 kg) |
6980 lbs (3173 kg) |
| Enclosure Rating |
NEMA 3R |
| Enclosure Finish |
Polyester powder coated steel; Optional stainless steel |